EL3061
DESCRIPTION:
The EL3061 analog input terminal processes signals in the range between 0 and 10 V. The voltage is digitized to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the EtherCAT Terminal have the reference ground as common ground potential. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.
TECHNICAL DESCRIPTION:
| Number of inputs | 1 (single-ended) |
| Power supply | via the E-bus |
| Signal voltage | 0…10 V |
| Distributed clocks | – |
| Internal resistance | > 130 kΩ |
| Input filter cut-off frequency | 1 kHz |
| Dielectric strength | max. 30 V |
| Conversion time | 0.625 ms default setting, configurable, multiplex |
| Resolution | 12 bit (16 bit presentation incl. sign) |
| Measurement error/uncertainty | < ±0.3% (relative to full scale value) |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption E-bus | typ. 130 mA |
| Current consumption power contacts | – |
| Bit width in the process image | inputs: 4 byte |
| Special features | activatable FIR/IIR filters, limit value monitoring |
| Weight | approx. 60 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Pluggable wiring level | for all ESxxxx terminals |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, cFMus |
| Ex marking | ATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |